향류형 냉각탑 내에서 충전재 특성값에 미치는 친수성 처리의 영향
김진호, 김서영, 강병하 · 1999
An experimental study for hydrophilic treatment effects on fill packings in a counterflow cooling tower has been performed. In the experimental results, the range increases as the water flowrate decreases, the air flowrate and the water inlet temperature increase. Hydrophilic treatment slightly enhances such effects but the influence is not prominent. As the air flowrate and the water inlet temperature increase and the water flowrate decreases, the fill packing characteristics are improved. These are caused by the contact area between air and water increased by hydrophilic treatment on fill packings. This paper presents KαV/L correlations for conventional and hydrophilic treatment fill packings as a function of air to water ratio.
Cited by 1 works.