실외 급배기구 크기와 이격거리에 따른 교차오염 특성연구
문용준, 노광철, 오명도 · 대한설비공학회 하계학술발표회 논문집 · 2006
This study is undertaken to evaluate the characteristics of cross contaminaion around exterior air-vents. A CFD analysis has been performed to calculate the cross contamination index for five exterior air-vents sizes according to the outdoor air velocity and separation distance of it. From the result of the numerical method, As the outdoor air velocity is increased, the cross contamination index is increased. on the contrary, as the separation distance of exterior air-vents is increased, the cross contamination index is decreased. additionally the cross contamination is affected by the aspect ratio of the size of exterior Air-vents