원관 표면에서의 서리층 물성치의 상관식

양동근, Min-Soo Kim, 이관수 · 대한기계학회 춘추학술대회 · 2005

In this paper, frosting experiments are conducted with variations of frosting parameters such as the air temperature, cold cylinder surface temperature, air velocity, and absolute humidity. Experimental results show that the local frosting behavior with increasing air velocity does not vary along the angular position. The dimensionless correlations for the thickness, density, and surface temperature of the frost layer and heat transfer coefficient are obtained as functions of the Reynolds number, Fourier number, absolute humidity, and dimensionless temperature by using a dimensional analysis. The applicable range of the correlations proposed in this paper is as follows: the air temperature of 3 to 9℃, cold cylinder surface temperature of -32 to -20℃, are velocity of 0.5 to 2.0 ㎧, and absolute humidity of 0.00282 to 0.00568 Kg/Kga.

Cited by 0 works.