수평관내 이산화탄소의 증발 압력강하

구학근, 손창효 · 대한기계학회 춘추학술대회 · 2005

The evaporation pressure drop of CO₂ (R-744) in a horizontal tube was investigated experimentally. The main components of the refrigerant loop are a receiver, a variable-speed pump, a mass flow meter, a pre-heater and an evaporator (test section). The test section consists of a smooth, horizontal stainless steel tube of 4.57 mm inner diameter. The experiments were conducted at saturation temperature of -5℃ to 5℃, and heat flux of 10 to 40 kW/m2. The test results showed that the evaporation pressure drop of CO₂ are highly dependent on the vapor quality, heat flux and saturation temperature. The measured pressure drop during the evaporation process of CO₂ increases with increased mass flux, and decreased saturation temperature. The evaporation pressure drop of CO₂ is much lower than that of R-22. In comparison with test results and existing correlations, the best fit of the present experimental data is obtained with the previous correlation. But existing correlations failed to predict the evaporation pressure drop of CO₂. Therefore, it is necessary to develop reliable and accurate predictions determining the evaporation pressure drop of CO₂ in a horizontal tube.

Cited by 2 works.