가스흡수식냉동기 세관제의 부식-침식거동에 관한 연구
임우조, 정기철, 윤병두 · 한국마린엔지니어링학회 학술대회 논문집 · 2003
This paper was studied on corrosion-erosion behavior of heat exchanger tube for gas absorption refrigeration machine. In the tap water at 30 ℃. anodic polarization test of copper and aluminium brass tube was carried out. And cavitation erosion-corrosion behavior of heat exchanger tube for gas absorption refrigeration machine were considered. The main results are as following: In the low anodic potential region, the corrosion current density of A1-brass is higher than that of Cu, but that of AI-brass is controlled than Cu over 350 m V /SCE from open circuit potential. The weight loss of copper by cavitation erosion-corrosion is higher than that of AI-brass. The pit growth behavior of copper by cavitation erosion-corrosion changes from shallow pit type to undercut pit type with time pass mg.
Cited by 0 works.