학교 건물에서 환기시스템에 의한 교실내 공기질 측정 및 성능평가

신희수, 이재근, 이재권 et al. · 대한설비공학회 하계학술발표회 논문집 · 2005

This paper describes to evaluate the performance of ventilation for investigating the removal of indoor pollutants as a function of ventilation rate and the number of occupants in the school classroom. Variations of the gas concentration as a function of time are measured at center point of classroom and air exchange rates with the CO₂ gas monitor. For the ventilator of 800 CMH in the classroom with the existence of 35 students, the average CO₂ concentration is 913 ppm. A ventilator of 800 CMH is sufficient to meet acceptable indoor air quality in the classroom of 35 students, a maximum number of students based on the Korea school standard below 1,000 ppm of CO₂.

Cited by 0 works.