이중관 히트파이프를 이용한 지열원 열펌프시스템에 관한 연구

장기창, 라호상, 이영수 · 2000

It was designed and manufactured geothermal combined system heat pipe and heat pump, and demonstrated it in our Institute. It was investigated the variation of underground temperature and the performance characteristics of long operation in geothermal heat pump system. When the temperature of heat sink was within 35~45℃, the heating capacity of geothermal heat pump system was about 4,000~4,800W and consumption power of compressor was indicated 1,600~1,700W. The COP of geothermal heat pump system was indicated about 2.4~3.0, therefore the performance of geothermal heat pump system is more excellent than that of air to air heat pump system.

Cited by 0 works.