공동주택에서 바닥 복사냉방 시스템과 외기전담시스템의 통합 적용 시 냉방 및 표면 결로 방지 성능 평가
김화국, 정창호, 여명석 et al. · 한국건축친환경설비학회 학술발표대회 논문집 · 2012
In this study, integration of dedicated outdoor air system and floor radiant cooling system were analyzed for precedent study to apply on domestic apartments. Considering volumetric load pattern of domestic apartments, cooling performance and condensation prevention of integrated system were evaluated with Trnsys 17 for dynamic simulation in cooling period.After the analysis of the result, room temperature was maintained at 26±1 ℃ without the condensation and the load ratio of two systems was 3.3 : 1 . Therefore, the cooling performance and condensation prevention of integrated system proved to be outstanding and further research on control may improve the efficiency of the energy performance.