지중배전케이블 준공시험 관련 국제규격 동향과 국내기준 개선 방안
李載奉, 鄭蓮賀, 宋一根 et al. · 2008
XLPE insulated power cables are introduced in Korea in 1980s. The cable installation test has been carried out according to the Korean Technical Reference of Electrical Facilities. But recent research results shows DC Hipot test cannot detect the serious defects in XLPE insulated cables. VLF test is recommended as a installation test of XLPE insulated cables by CENELEC and IEEE standards in 1996 and 2001 respectively. We suggest to apply VLF test as an installation test for XLPE insulated MV cables in Korea.
Cited by 0 works.