탄산칼슘 농도에 따른 이중관 열교환기의 세정 특성

채희만, 차동안, 권오경 et al. · 대한설비공학회 동계학술발표회 논문집 · 2014

This research was conducted to confirm cleaning characteristics of double pipe heat exchanger according to concentration CaCO 3 . The fouling was generated by artificially making CaCO 3 form CaCl 2 and NaHCO 3 for 600 minutes. The fouling concentration varied from 1000, 2000 and 3000 ppm. The double pipe heat exchanger was cleaned by inserting a sponge ball after CaCO 3 fouling. The overall heat transfer coefficient recovered 98.8% for 1000 ppm case, 92.5% for 2000 ppm case and 90.5% for 3000 ppm case in comparison with initial state. It can be concluded that the cleaning of sponge ball contribute significantly to the of performance recovery for overall heat transfer coefficient and fouling resistance after cleaning experiment.