This paper presents operating characteristics of natural refrigerant geothermal heat pump system. Variation of operating conditions are refrigerant charge amount, EEV opening, compressor frequency, secondary fluid temperature and flow rate. The results show that optimum refrigerant charge amount of the system is 2400 g and optimum EEV opening is 20% in the cooling mode and 16% in the heating mode. In the case of variation of compressor frequency, cooling capacity increases but COP decreases with the increase of compressor frequency.