에어컨 열교환기의 공기측 파울링 특성 연구
안영철, 조재민, 이재근 et al. · 대한설비공학회 학술발표대회논문집 · 2002
Heat exchangers are used widely in residential, commercial and industrial HVAC applications. Indoor and outdoor air contaminants foul these heat exchangers. Fouling of heat exchangers can cause decreased cooling capacity and efficiency of the HVAC equipment as well as degrading indoor air quality. The objective of this research is to investigate the cooling performance and pressure drop in the air-side particulate fouling of heat exchangers for air conditioners. 30 samples of air conditioners being used in the field such as inn, restaurant, beauty shop, and office are collected in chronological used order. Test results show 15% decrease of the cooling capacity and 44% increase of the pressure drop for the air conditioners used in the seaside inn.
Cited by 0 works.