프리스트레스트 와이어로프로 비부착 보강된 콘크리트 벽돌 조적벽의 내력 및 연성
양근혁, 주대봉, 변항용 · 대한건축학회 논문집 - 구조계 · 2011
Three full-scale retrofitted unreinforced masonry (URM) walls and an unstrengthened URM wall were tested under constant axial load and cyclic lateral loads in order to evaluate the effect of a strengthening procedure developed using unbonded prestressed wire rope units on enhancing the in-plane shear strength and ductility of unreinforced concrete brick masonry walls. The spacing of wire ropes varied between 150 ㎜ and 450 ㎜ at the constant wall aspect ratio of 0.85. The ductility of the walls tested was evaluated using the work damage indicator, suggested by Sheikh and Khoury, calculated at each loading step from the hysteretic loops. The in-plane shear strength of walls tested was also compared with predictions obtained from the simple equations proposed to identify the shear transfer capacities of masonry and wire ropes. Test results showed that the developed strengthening procedure was highly effective in enhancing the shear cracking strength, ultimate shear strength and ductility of URM walls and controlling crack propagation along head and bed mortar joints. Higher shear strength and work damage indicator were observed in the retrofitted URM walls than in unstrengthened URM wall by 2.85 and 3.48 times, respectively, for sw of 150 ㎜, by 2.41 and 3.08 times, respectively, for sw of 300 ㎜ and by 2.05 and 2.14 times, respectively, for sw of 450 ㎜, where sw is the spacing of inclined wire ropes. The shear capacities predicted from the proposed simple equations were in good agreement with test results.