수력발전기 고정자 권선의 운전중 부분방전 특성

金熙東, 金秉漢 · 전기학회논문지 C · 2006

During normal machine operation, partial discharge(PD) tests were performed with partial discharge analyzer(PDA) in two hydrogenerators. Six cable couplers were installed in circuit ring bus and endwinding of three phases. PDA showed that the normalized quantity number(NQN) and the partial discharge magnitude(Q m ) were very low in hydrogenerator #1 and #2, respectively. The trend analyses of NQN and Q m value are available for monitoring of the insulation condition in hydrogenerator stator windings. The insulation condition of stator winding can be assessed. Discharge at conductor surface was discovered in B phase(C2 coupler) of hydrogenerator #1. Internal discharges were generated in A and C phases(C2 coupler) of hydrogenerator #1 and in A, B and C phases(C1 and C2 couplers) of hydrogenerator #2. Slot discharges occurred in A, B and C phases(C1 coupler) of hydrogenerator #1. The stator windings of two hydrozenerators were in good condition.