하이브리드 제습기의 입구조건, 재생조건, 로터회전수에 따른 영향 분석을 위한 사이클 해석
서정남, 김영일, 박승태 · 대한설비공학회 하계학술발표회 논문집 · 2010
Hybrid dehumidifier is a combined system of refrigeration and desiccant dehumidifier and though complicated, it is considered to be more efficient than the individually operated dehumidifying system. In this work, cycle analysis using EES and Eco-dry programs is done to study the effect of inlet condition, regeneration condition and rotor rotation rate on exit temperature, exit humidity and dehumidification effectiveness of a hybrid dehumidifier. Cycle simulation shows that dehumidification effectiveness and dehumidified quantity is greatest when regeneration flow rate ratio is in the range of 0.3-0.5. The dehumidification effectiveness becomes maximum when the rotor rotation rate is 2-3 rph.