[論文] 室內 濕度 增加를 利用한 無再熱 冷房시스템 改善에 關한 硏究
이흥주, 김용구 · 설비저널 · 1987
In a room air conditioning cooling system, if the room-sensible-heat-factor as plotted on a Psychrometric Chart intersects the saturation curve below the apparatus leaving air dewpoint, reheat must be used to maintain the design room air conditions. However, if the design room humidity is permitted to be raised to some degree, the cooling system will not require reheat as a new room-sensible-heat-factor line is developed between the apparatus leaving air dew-point and the adjusted design room air condition point. The advantages to this are the cost of reheat equipment and operation can be avoided. The cycle of this system can be shown on a Psychrometric Chart to plot the design condition points.
Cited by 0 works.