권선형유도발전기를 갖는 신재생에너지 시스템을 위한 전압벡터 동기화 기법
朴正雨, 李基旭, 金東旭 · 2007
In order to transmit energy generated through the stator winding of a doubly-fed induction generator (DFIG), we need to synchronize the generated voltage vector with the grid voltage vector. However, the existing synchronization methods work only when the encoder is installed at a specific position and equivalent constant is precise. In order to solve this problem, a new synchronization method has been proposed and a way of applying the method to existing doubly-fed induction generator control algorithm has been also proposed. The validities of the methods proposed were verified by using a prototype converter for a 1.5㎿-class doubly-fed induction generator and experimental results showed the validity of that against variation of an encoder positions, generator parameters, and grid voltages.
Cited by 0 works.