데이터센터 외기 냉각시스템의 실험적 연구
최병남, 김학근, 김은기 et al. · 대한설비공학회 동계학술발표회 논문집 · 2013
The main purpose of this research is to investigate the cooling energy performance and fluid behavior on cold and hot aisle of modular data center. The thermal characteristics of designed cold and hot aisle configuration was evaluated by computational fluid dynamics(CFD). The cooling energy performance of the modular data center was experimentally analyzed by using mock-up test bed. The results showed that the air could be uniformly distributed through the cold and hot aisle. And the setpoint temperature of cold aisle(supply air) could also be well maintained by modulating the damper operation for mixing the outdoor air and return air. Consequently, the PUE during experimental tests on mock-up test bed showed 1.07 to 1.08.