한전 초전도전력케이블 시스템의 열부하 측정시험
양형석, 김동락, 손송호 et al. · 대한기계학회 춘추학술대회 · 2008
A system for the 3-phase 100-m HTS power cable with 22.9㎸/1.25㎄ has been tested at the KEPCO뭩 Gochang power testing center since 2006. The cooling system consists of a liquid nitrogen decompression cooing system with a cooling capacity of 3㎾ at 66K and a closed circulation system of subcooled liquid nitrogen. Heat loads of the KEPCO HTS power cable system for several electrical loads were measured for investigating long-term operating performance such as cooling capacity, heat load, AC loss, temperature stability of the system.