수평관내 이산화탄소의 증발 열전달 특성

손창효, 이동건, 김영률 et al. · 대한설비공학회 하계학술발표회 논문집 · 2004

The evaporative heat transfer coefficient of CO₂(R-744) in a horizontal tube was investigated experimentally. The experiments were conducted without oil in a closed refrigerant loop which was driven by a magnetic gear pump. The main components of the refrigerant loop are a receiver, a variable-speed pump, a mass flow meter, a pre-heater and evaporator(test section). The test section consists of a smooth, horizontal stainless steel tube of inner diameter of 7.75㎜. The experiments were conducted at mass flux of 200 to 500㎏/㎡s, saturation temperature of -5 to 5℃, and heat flux of 10 to 40 ㎾/㎡. The test results showed the heat transfer of CO₂ has a greater effect on nucleate boiling more than convective boiling. Mass flux of CO₂ does not affect nucleate boiling too much, and the effect of mass flux on evaporative heat transfer of CO₂ is much smaller than that of refrigerant R-22 and R-134a. In comparison with test results and existing correlations, correlations failed to predict the evaporative heat transfer coefficient of CO₂, therefore, it is necessary to develope reliable and accurate predictions determining the evaporative heat transfer coefficient of CO₂ in a horizontal tube.