핀 표면의 물접촉각이 열교환기 압력강하에 미치는 영향 연구

안승표, 이현욱, 오정근 et al. · 대한설비공학회 학술발표대회논문집 · 2001

Generally, air side pressure drop is known to be dependent on the surface wettability of the finned tube heat exchangers of air conditioning system. Thus many hydrophilic coated materials are applied to heat exchangers to decrease pressure drop in the wet conditions. Filmwise condensation occurs on good hydrophilic surfaces with a smaller contact angle. In the present experimental study, the wet characteristics of dehumidifying finned tube heat exchangers with various surface wettability are investigated. It is proposed that the air side pressure drop ratio (ΔPwet, ΔPdry) can be correlated with advancing dynamic contact angle and water droplet diameter.