Wilson plot기법을 이용한 2중관식 대향류 열교환기의 단상 열전달에 관한 연구
엄기찬 · 2006
An experimental study of a counterflow heat exchanger was performed. The heat exchanger had an effective heat transfer length of 1000㎜ and was operated in a counterflow arrangement with hot water(30±0.5℃, Re i =3500~20000) in the inner tube(copper tube, d?=9.52㎜) and cold water(15±0.5℃, Re DH =10700~39000) in the annulus(copper tube, D?=19.05㎜). Overall heat transfer coefficients were calculated and heat transfer coefficients in the inner tube and the annulus were determined using Wilson plots. The inner Nusselt number was compared with that of Gnielinski's correlation and they agreed within ±10% error. The trends were typical for a fluid-to-fluid heat exchanger with the overall heat transfer coefficient increasing with both inner and annulus flow rates. In the range of this experiment, Nusselt numbers for the inner tube flow were almost identical with those of the annulus flow at the same Reynolds number.