변유량 펌프 패키지 시스템 적용 사례 연구
유해성, 박형준 · 대한설비공학회 동계학술발표회 논문집 · 2009
This case study of secondary pumping system presents how important a design of an existing campus-type chilled and hot water system is these complex systems. One of the most important advantage of variable speed pumping package system with dynamic balancing is the elimination of over-pressuring of the buildings near the central plant. This paper is described by the use of the buildings piping analysis is a flow rate table for this system as a primary-secondary system at full design load. A variable speed pumping package system have user-friendly controller as touch screen and using the differential pressure both of inlet and outlet at zone, provide variable flow. This control system functions are auto staging optimization, alternating control and variable functions. This pumping system has the advantage of saving energy for many kinds of energy systems than those of the water system.
Cited by 0 works.