용량가변 시스템 에어컨의 냉방운전 시압축기 토출온도 상관식
이상헌, 권영철, 장근선 et al. · 대한기계학회 춘추학술대회 · 2006
An experimental study has been performed to investigate the correlation on compressor discharge temperature of capacity modulated system A/C in cooling mode. Indoor and outdoor temperatures, the cooling capacity, compressor discharge temperature and loading time are measured by the psychrometric calorimeter. The system is controlled by applying the scroll compressor, which is operated by PWM valve and loading duty. With decreasing outdoor temperature, the cooling capacity increases. But, with decreasing indoor temperature, it decreases. Also, with increasing loading duty the cooling capacity increases. According to the increase in outdoor temperature and loading duty, compressor discharge temperature increases. From these experimental data, the correlation on compressor discharge temperature is proposed. It is expressed as a function of indoor temperature, outdoor temperature, and loading duty. The correlation obtained from the present study is agreed with the experimental data within 3℃.