팬코일용 열교환기 회로변경에 따른 실험적 연구

이상재, 이윤수, 권영철 et al. · 대한기계학회 춘추학술대회 · 2001

The purpose of this study was to investigate the heat transfer characteristics of FCU(fan coil unit) heat exchanger, using Air-enthalpy Calorimeter. Experiments were carried out by changing air flow rate and water flow rate for φ 9.52㎜ heat exchanger with slit fin under cooling condition. The results show that the heat flux increases about 12% as changing circuit path(from 2 row series circuit to 1 row parallel circuit). The Capacity of sample 2 was about 28% as air flow rate and about 25% as water rate higher than that of sample 1. Also, j-factor of test condition A was better, compared with test condition B and f-factor of sample 2 was better since the pressure drop as changing circuit path.