히트파이프와 열전소자가 결합된 일체형냉각모듈 개발에 관한 연구

고광수, 박윤철, 고원빈 et al. · 대한설비공학회 2013년도 하계학술발표대회 · 2013

In this study, a combined thermoelectric device and a heat pipe cooling module performance test was conducted to determine the heat transfer characteristics of the cooling module at a condition of given room temperature with cooling airflow 1 ㎥/min. As results, the thermal dissipation is up to 624W at the given air flow condition. It has no increment even the air flow increased at the same room temperature due to the temperature limitation of the thermoelectric device.

Cited by 0 works.

Authors