대심도 지하역사에서의 화재시 연기거동과 피난에 대한 수치해석 연구
김홍진, 배승용, 최영기 et al. · 한국철도학회 학술발표대회논문집 · 2011
Advantages of the deeply underground subway are underground space efficiency, high speed, decrease of noise and vibration. However, when fire occurs in the deeply underground subway station, large casualties are occurred like Daegu subway station fire due to the increase of evacuation distance. In this study, a numerical analysis was performed by using the fire and evacuation analysis program FDS+EVAC for smoke movement and evacuation in Beotigogae station among the deeply underground subway station. Heat release rate of carriage fire was set 10MW and the fire growth rate was ultrafast. As a result, the smoke move to the exit at 1085 second. The total evacuation time took 956 second.
Cited by 0 works.