에어컨 실내기 직교류팬의 공력소음에 대한 소음원의 수치해석적 분석
민윤홍, 강성원, 허남건 et al. · 대한기계학회 춘추학술대회 · 2012
In the present study, analyze of the noise source was conducted from prediction of aerodynamic noise of cross-flow fan (CFF) in air-conditioner (AC) indoor unit. For accurate prediction of vortex caused the aerodynamic noise, 3-D computation and large eddy simulation (LES) were adopted. The Ffowcs Williams-Hawkings (FW-H) equation, which is one of the acoustic analogy methods for far-field acoustic pressure, was used to predict aerodynamic noise. The sound pressure level (SPL) result of the predicted total noise of AC indoor unit was good agreement with a valid experimental data. The stabilizer, rear guider and blades in AC indoor unit were considered for the main noise source, and each SPL spectra were compared with the tonal noise to analyze the noise source. The dominant component was different as frequency band. Especially, the blade passing frequency (BPF) peak and broadband noise were most affected by the blades. The result also showed flow characteristics caused tonal and broadband noise.
Cited by 0 works.