Micro gas turbine (MGT) has received attention recently as a small-scale distributed power source. Due to many advantages such as their small size, low maintenance cost and minimal vibrations during operation, they are expected to become widespread in a wide range of applications. The exhaust heat emitted by the MGT is in the form of an exhaust gas that is about 270℃ which is an extremely clean gas. Korea Gas Corporation (KOGAS) has researched performance characteristics of a cogeneration system combining 28 ㎾ class MGT and 13 USRT class absorption hot and chilled water generator in the local condition. The present results of this study can be summarized as follows: (1) in heating mode, the total efficiency of cogen. system is about 65% and heating capacity is 33 ㎾ at 25 ㎾ MGP power (2) in cooling mode, COP is about 0.6 at 22 ㎾ MGT power.