헬리컬관외 침전 및 적하 열전달 특성에 관한 연구
황승기, 윤상국, 김동혁 et al. · 설비공학논문집 · 2001
An experimental study is carried out to investigate the characteristics of heat transfer of outside helical tubes. The main heat exchanger consists of twelve curved columns with each 300 ㎜ diameter and the total length of 1.2m copper tube having an outer diameter of 19.05 ㎜ with 1.5 ㎜ thickness. Water flows down the outside of helical tube, where flow patterns are the vertical film falling flow, immerged flow, and mixed-flow which is the combination of film falling flow and immerged flow. Refrigerant 11 flows the inside of the tube countercurrently. The experimental range of inside flow rate is 1.7~3.2 l/min and outside flow rate is 21~33 l/min. The results are presented as Nusselt number with corresponding Reynolds number for variety of outside and inside flow rates. The heat transfer rates of the mixed flow are 8 to 56% higher than those of film falling flow or immerged flow only. Interpretation of the results is given on the basis of physical reasoning and the correlation equations.