하천수 열원 이용 열펌프 시스템의 LCC 분석
한상수, 박차식, 김용찬 · 대한설비공학회 학술발표대회논문집 · 2009
The performance of a heat pump using river water as a heat source was compared with that of a conventional air-conditioner for cooling and a boiler system for heating. The heat pump system using river water considered the 1-stage cycle for cooling and the 2-stage cycle for heating. The COPs of the river water source heat pump were 0.5~ 1.1 higher than those of the conventional system in the cooling season. The LCC of the river water source heat pump system was lower 13.5% and 32.4% than that of the conventional system Ⅰand Ⅱ. In addition, when the initial cost ratios of the river water source heat pump system to the conventional system Ⅰand Ⅱ were less than 1.2 and 1.4, respectively, an acceptable payback was found to be less than 5 years.
Cited by 0 works.