단위세대 제어방법이 난방순환수 반송동력 소비에 미치는 영향

이태원, 김용기 · 대한기계학회 춘추학술대회 · 2009

In most of the residential buildings in Korea radiant heating system has been used circulating hot water through coil of the floor panel. Thermostatic valves for room temperature control should be installed since 1990's to save heating energy, but there are few material to refer to select proper product for each household. In this study numerical analysis was carried out with the mathematical model on the heating space and control methods or control valves to estimate the rate of hot water consumptions per unit heat supplied to treat the heating load, which effect on the pumping loss greatly, for various weather condition and operating parameters, such as outdoor air temperature, the temperature and the volumetric flow rate of circulating hot water. As results the unit hot water consumptions were compared for several control methods, on/off and PID control of the room temperature and PID control of the return water temperature.

Cited by 1 works.