인위적인 자외선 조사량에 따른 폴리머애자에서의 코로나 방전 특성
김영석, 최명일, 김종민 et al. · 2013
In this study, degradation was observed by irradiating UV rays to the polymer insulators which have been widely used in outdoor electric power facilities. For an indoor accelerated UV test, 0.55 w/m2 of UV rays were applied using a xenon-arc method. A UV detection system with 65 O㎜ in diameter, 100 ㎜ in length and 1.0 of brightness (F/#) has been designed. Even though efflorescence on the surface of polymer insulators wasnt observed according to the accelerated UV test. UV rays were detected at around 50% and 40% of insulation breakdown in EPDM and silicone-type insulators respectively. As degradation continued because of an indoor accelerated UV test, breakdown voltage with which UV rays can be detected in an early stage decreased as well. A silicone polymer insulator would be severer than EPDM polymer insulator in terms of surface degradation because of UV strength against Vm/VBD was high in silicone polymer insulators. UV strength in silicone-type insulators increased at 1,000 kJ/㎡ because contact angle at the intial stage sharply decreased to from 113° to 92.1°
Cited by 3 works.
Authors
References
- Daylight corona discharge imager
- A criterion for UV detection of AC corona inception in a rod-plane air gap
- The Characteristics of UV Strength According to Corona Discharge From Polymer Insulators Using a UV Sensor and Optic Lens
- 과도방사선 검출을 위한 핵폭발 검출기 제작 및 검증
- Preventive inspection of line insulators through corona emission: A case study
- Comparison of the Poor Insulator Detecting Technique for the Reliability Enhancement of the Electric Power Facilities
- A Study on the Ultraviolet Aging Characteristics of Outdoor Polymeric Insulating Materials