판형 열교환기의 압력강하와 총괄열전달계수 특성에 관한 연구
김기수, 송영호, 최두열 et al. · 대한기계학회 춘추학술대회 · 2010
At present, a plate heat exchanger (PHE) has been widely used in the various engineering fields due to its compactness. It was first adopted in the food industries from 1930. As well known, it has excellent features such as high heat transfer efficiency, easy expandability on a site and so on compared with a conventional shell & tube heat exchanger (STHE). Especially, easy increase of a heat transfer area on a site makes it more preferred for the various industries to use the PHE than the STHE because the heat transfer area of a PHE can be increased by inserting the plates on a site when the temperature control is failed in a commissioning stage. Therefore, many engineers or operators have tried to solve the problem with an easy and naive solution to increase the number of plates when facing with the failure of a temperature control of the PHE. However, from the recent our experiences, the increase of the plates are not the best cure for solving the poor heat transfer rate of it. The increase of the plates brings to lower the flow velocity in a channel and then it reduces the Reynolds number, which means that the overall heat transfer coefficient (OHTC) of the PHE is decreased contrary to our expectation. In this study, we tried to make clear the relation between the increased heat transfer area and the decreased OHTC brought by adding the plates on a site. The results of this study indicate that the engineers to design or operate the PHE should find out the compromise between the increased heat transfer area and the decreased OHTC.
Cited by 0 works.