헬리컬형 코일 관외 열전달 특성에 관한 실험적 연구

황승기, 윤상국, 최광호 et al. · 대한설비공학회 학술발표대회논문집 · 1999

An experimental study is carried out to investigate the characteristics of heat transfer of outside helical tubes. The main heat exchanger consists of a twelve curved columns of each 300㎜ diameter, and the total length of 1.2m copper tube having an outer diameter of 19.05㎜ and 1.5㎜ thickness. Water flows down the outside of helical tube, of which flow patterns are the vertical film falling flow, immerged flow, and mixed-flow which are film falling and immerged flows partly combined. Refrigerant-11 flows the inside of the tube countercurrently. The experimental range of the inside flow rate is 1.7~3.2l/min, and its outside flow rate, 21~33l/min. The results are presented as dimensionless Nusselt numbers with the corresponding Reynolds numbers for a variety of outside and inside fluid flow rates. The heat transfer rates of the mixed flow were 8 to 56% higher than those of film falling flow or immerged flow only. Interpretation of these results is given on the basis of physical reasoning and the correlation equations.