시간-주파수 영역 반사파 계측법 기반 활선 상태 지중 전력 케이블의 중성선 결함 위치 추정 연구
이춘구, 윤태성, 박진배 · 2013
In this paper, we propose a time-frequency domain reflectometry (TFDR) based measurement method for localizing concentric neutrals corrosion on live underground power cable. It consists of two inductive couplers which can transmit the reference signal into live underground power cable and measure the reflected signals from the impedance discontinuities of concentric neutrals corrosion. In order to compensate the dispersion of the measured reflected signal via inductive coupler, an equalizer based on Wiener filtering is designed. To improve the localizing performance of concentric neutrals corrosion in the vicinity of the measurement point, the reference signal is removed from the measured reflected signals. The localization performance of the proposed method is verified by the concentric neutrals corrosion localization experiment.
Cited by 0 works.
Authors
References
- Application of Time-Frequency Domain Reflectometry for Detection and Localization of a Fault on a Coaxial Cable
- An Optimization Criterion for Iterative Deconvolution
- Detection and Location of Multiple Wiring Faults via Time–Frequency-Domain Reflectometry
- Analysis of the Combined Effects of Load Cycling, Thermal Transients, and Electrothermal Stress on Life Expectancy of High-Voltage AC Cables
- Application of joint time–frequency domain reflectometry for electric power cable diagnostics
- Discrete time and frequency Wigner-Ville distribution: Moyal's formula and aliasing
- A Study on Long Range Image Monitoring and Tracking System Using Laser Range-Gate Method in Inclement Weather Conditions