Fast Decoupled Load Flow
B. Stott, O. Alsaç · IEEE Transactions on Power Apparatus and Systems · 1974
This paper describes a simple, very reliable and extremely fast load-flow solution method with a wide range of practical application. It is attractive for accurate or approximate off-and on-line routine and contingency calculations for networks of any size, and can be implemented efficiently on computers with restrictive core-store capacities. The method is a development on other recent work employing the MW-Θ/ MVAR-V decoupling principle, and its precise algorithmic form has been determined by extensive numerical studies. The paper gives details of the method's performance on a series of practical problems of up to 1080 buses. A solution to within 0.01 MW/MVAR maximum bus mismatches is normally obtained in 4 to 7 iterations, each iteration being equal in speed to 1½ Gauss-Seidel iterations or 1/5th of a Newton iteration. Correlations of general interest between the power-mismatch convergence criterion and actual solution accuracy are obtained.
Cited by 1,522 works. doi:10.1109/tpas.1974.293985
Authors
References
- Power Flow Solution by Newton's Method
- Direct solutions of sparse network equations by optimally ordered triangular factorization
- Computer Methods in Power System Analysis
- Optimal Load Flow with Steady-State Security
- Iterative Linear AC Power Flow Solution for Fast Approximate Outage Studies
- Introduction to Numerical Analysis
- Further developments in Newton’s method for power system applications.
- Automatic Adjustment of Transformer and Phase-Shifter Taps in the Newton Power Flow
- Decomposition of Real and Reactive Power Flows: A Method Suited for On-Line Applications
- Decoupled Newton Load Flow