공동주택의 한국형 온돌시스템 적용에 관한 연구

안민희, 최창호, 유기형 et al. · 대한설비공학회 학술발표대회논문집 · 2006

The traditional Korean Ondol System that is a radiant floor heating system was made as warm floor and cool indoor temperature. Nowaday, Ondol is developed as the hydronic floor heating system. But unbalance of floor temperature and indoor temperature is occurred because strengthen thermal insulation and airtightness in building changes thermal performance. To solve these problems, we examine actual indoor environment of heating system methods in existing apartments and present the new method of floor heating system. The existing heating system made definite indoor temperatures but floor temperatures that is 22℃-26℃was maintained. To solve these problems, we adopted the differential heating system which made warm area and cool area. A differential heating system was made different pitches of heating pipe in single zone and ratio of warm area to cool area is 1 to 2. As a result of experiments, warm area temperature is 40.7℃, cool area temperature is 36.1℃. A difference of temperature between both area is 4K. A distribution of indoor vertical temperature is similar to both warm area and cool area.

Cited by 0 works.