압축기 용량조절범위에 따른 인버터형 열펌프의 계절성능에 관한 실험적 연구

하도용, 박윤철, 민만기 · 대한설비공학회 학술발표대회논문집 · 1997

An experimental study was conducted on the effect of compressor capacity control range of heat pump on the seasonal energy efficiency ratio with variation of the maximum and minimum compressor input frequencies. To obtain seasonal energy efficiency ratio, steady state test at the maximum, minimum and intermediate compressor speed and cyclic test at the minimum compressor speed should be conducted. Maximum input frequency was varied to 95㎐, 105㎐, 115㎐ and the minimum input frequency was varied to 35㎐, 45㎐, 55㎐. The seasonal energy efficiency ratio increased as the input frequency to the compressor decreased. The maximum input frequency had only slight effects on the SEER.

Cited by 0 works.