Experiments were carried out to study the characteristics of a thermosyphon in a regenerator with a surface-flame burner for a lithium bromide (LiBr)-water absorption heat pump. A cylindrical-shape metal-fiber burner and commercial grade propane were used. The generation rate of water vapor as a refrigerant was measured. It could be using as a reference value representing the performance of a regenerator. The circulation rate of the LiBr-water solution was also measured from both the tanks for the weak- and the strong-solution. Using a refractometor, the LiBr concentration in the solution was calculated from the measured refractory index of the solution. Temperature of the solution and the condensed water was recorded at several points in the experimental apparatus with thermocouples, using a personal computer. The generating rate of water vapor increased slightly with increasing delivery height of the solution in tubes but it decreased after the delivery limit of the thermo-syphon tubes. The circulating rate of LiBr solution decreased rapidly with increasing delivery height of the solution, and the decreasing rate became larger around the delivery limit. The limit of delivery height increased with heat input, but the ratio of the circulation rate of the solution to the generating rate of water vapor increased suddenly at the limit of delivery height. The difference between LiBr concentrations in the weak and the strong solution depends on the circulating rate more than the vapor generating rate.