핀 형상에 따른 폐열회수용 열교환기 성능 시험
맹재훈, 남명환, 전용두 et al. · 대한설비공학회 하계학술발표회 논문집 · 2010
Fin tube heat exchangers have been used in many industrial applications. In the waste heat recovery applications, however, the selection of high performance fin shapes are challenged by the adverse operating conditions as high humidity and fouling sources. In this study, the heat recovery performance of different fin shapes (plain, spiral, twist, curved wavy) are experimentally studied in terms of the total heat transfer and the associated pressure drop. For this study the water inlet temperature was set to 60℃(±1) while the gas inlet temperature ranged from 150∼165℃ depending on the flow rates that correspond to the Reynolds number(R eD,m ) from 2,373∼3,230. According to the tested results, the wavy fins(6 fins/inch) showed the superior performance in terms of goodness factor, F G (=(Q/Q max )/( △P/P atm )), although the plain fins showed the highest total heat transfer performance. Among the test fins, the spiral fins(8 fin/ inch) showed the lowest values in goodness factor.
Cited by 0 works.