이중관형 열교환기의 응축 열전달 특성에 관한 실험적 연구
이권재, 권오경, 김용찬 et al. · 대한설비공학회 동계학술발표회 논문집 · 2012
An experimental investigation was carried out to examine the condensation heat transfer characteristics in the double pipe heat exchanger using R-410a. The double pipe heat exchanger was helical coil type. The inner tube of double pipe heat exchanger was two types, spiral and circle. The experimental runs were carried out at a saturation temperature of refrigerant ranging 50℃, and mass fluxes are 154.8~206.6 kg/m2s. The inlet temperature of the water in the test section were 35℃ and 40℃. Heat transfer coefficient of refrigerant side of spiral type and circle type were 1.8 kW/m2℃ and 2.6 kW/m2℃ at mass flux 206.6 kf/m2s. The pressure drop of refrigerant side for circle type was higher than that of spiral type.