외기냉수냉방의 운전사례 및 에너지 절감량 분석

김범수, 김영일, 권용일 et al. · 대한설비공학회 하계학술발표회 논문집 · 2010

Due to high insulation and increased internal heat generation, some buildings require cooling even during winter seasons. One simple way of saving cooling energy consumption is to use a free cooling system when the outdoor air temperature is low. With free cooling system, cooling water is recirculated through the cooling tower to be cooled by the cold outdoor air without operating the chillers. This cooled water is used to cool the indoor space. The operation data of two buildings which utilizes the free cooling system are collected and analyzed. The analysis shows the free cooling system can save energy about 55% compared to the turbo chiller system.

Cited by 0 works.