자연급기구내 플리머필터 설치 시 외기 침기량 분석에 관한 연구
이성환, 최종악 · 대한설비공학회 학술발표대회논문집 · 2009
This test was progressed in the test house of KICT as sectional research of Center for Sustainable Housing. It included a ventilation rate of hybrid ventilation equipment, temperature, and gas test using the SF-6. The purpose of this test is to demonstrate the performance of viovent by estimating an outdoor air flow rate through viovent which the flimmer filter is installed and decide the leakage after operating the constant airflow fan within a house. First, the outdoor airflow rate through viovent measured 130 ㎥/h more than a legal required ventilation rate, 104 ㎥/h. And then it sufficiently satisfy a legal standard, 0.7 air change/h. Secondly, the result of this test exposes that the leakage in the residence is about 20~25%. Especially, the outdoor air flowing through the gate occupies 50% of the total leakage.