전열판 수에 따른 판형열교환기의 전열특성에 대한 실험적 연구
송찬호, 윤석호, 김욱중 et al. · 대한설비공학회 학술발표대회논문집 · 2012
The present study has been conducted about plate heat exchanger with different plate number. The heat exchanger is used for heating water system operating by heat pump and is gasket type PHE. The required design points such as allowable pressure drop, heating capacity are considered and some experimental results are analyzed. The test plate number is 6, 10, 20, and pressure drop and heat transfer test are performed. Under the allowable pressure drop, it can be proposed that the plate heat exchanger should have about 16 plates and it should also be designed considering product cost by adding plates.