프리캐스트 콘크리트와 현장타설 콘크리트 복합 보의 전단강도

김철구, 박홍근, 홍건호 et al. · 한국콘크리트학회논문집 · 2013

Currently in precast concrete construction, precast concrete and cast-in-place concrete with different concrete strengths are used. However, current design codes do not provide shear design methods for PC-CIP hybrid members using dual concrete strengths. In the present study, the shear strengths of beams using dual concrete compressive strengths (24 MPa, 60 MPa) were tested. The test variables were the area ratio of the two concretes, longitudinal bar ratio, and shear span-to-depth ratio. The shear strengths of test specimens were evaluated by current design methods, using an effective concrete strength (considering the area ratio of the two concrete strengths). The test result showed that when 60 MPa concrete was used in the compressive zone and the longitudinal bar ratio was low, the shear strengths of the test specimens were less than the predictions. On the basis of the results, design recommendations were provided for the shear design of the PC-CIP hybrid beams.