고온 및 저온 열교환기용 판형 열교환기의 형상에 따른 열전달 성능 비교
오재경, 하옥남, 조홍현 · 대한설비공학회 학술발표대회논문집 · 2012
The performance of various type plate exchangers with different chevron angle, dimple size and arrangement was analysed by using Ansys v13.0. Heat transfer performance, pressure drop and flow patten of plate heat exchanger were investigated according to mass flow ratio. As a result, the 60°-chevron type plate heat exchanger showed the highest heat transfer performance but pressure drop was relatively high. Among dimple type plate heat exchangers, the highest heat transfer performance was shown in a dim_zigzag type plate heat exchanger but pressure drop was very high. Besides, the dim_upsize plate heat exchanger showed very low pressure drop.