슬릿 및 루버핀의 열 및 유동 특성에 대한 실험적 연구
이욱용, 김현영, 하삼철 et al. · 대한설비공학회 학술발표대회논문집 · 1998
This paper presents experimental results of heat and mass transfer phenomena and air-side pressure drop which takes place on the surface of slit and louver fin under the dry and wet air condition. In this research, we used fin and tube heat exchanger having 2 row of O 7. The sensible heat transfer coefficient of slit fin is higher than that of louver fin in both cases of 1st row and 2nd row. The latent heat transfer coefficient is higher than that of louver tin except below a certain mass flux. The air-side pressure drop of slit fin is higher than that of louver fin both dry and wet condition. In the wet air condition, the more increases FPI, the more decreases the air-side pressure drop of slit fin compared to dry air condition. But the ratio of pressure drop of louver fin increase as the FPl increases.
Cited by 0 works.