동절기 온실의 열 손실에 관한 실태조사

임재운, 윤성욱, 김현태 et al. · 2013

An experiment was conducted to study incidences of heat loss in greenhouse in Gyeongnam province using thermal imaging camera in order to determine ways minimizing greenhouse heat loss. Measurements of this work showed that temperature differences between two experiment zones before and after installation of thermal curtains were about 2.0~3.0℃ and 1.0~2.0℃ respectively. There was a high correlation between the temperature data measured using a thermal imaging camera and a temperature sensor. There was no serious difference among areas, but between places on the first and second floor with thermal curtains for heat insulation, there was a relatively larger heat loss on the first floor than the second floor. Then in general the greenhouse types had no particular bearing on this matter, there was a relatively large heat loss in the parts of side wall window, the gaps and the parts folded of horizontal thermal curtains, the gutter parts, and the gaps of thermal curtain in the side wall window and facade·back side for heat insulation, aren’t completely sealed. It was found that there was a substantial heat loss due to infiltration through cracks on covering material, doors, ventilating openings, roof gables and floors, in particular.