가스 인젝션 난방사이클에서 시스템 운전조건의 변화가 최적충전량 형성에 미치는 영향
허재혁, 정민우, 김보성 et al. · 대한기계학회 춘추학술대회 · 2008
For heat pumps used in the cold region, it is very important to obtain appropriate heating capacity. Gas injection technique has been proved as an effective method to enhance heating capacity of a heat pump operated in cold climate. Several control devices should be implemented into the gas injection cycle due to a wide operating range of the system. In this study, a gas/liquid separator was used to inject vapor refrigerant into the twin rotary type compressor. In addition, two EEVs and an injection valve were installed to control the refrigerant flow rates in the main and injection loops. Although the gas injection cycle operates at various operating conditions, refrigerant charge amount should be fixed. Therefore, it is very important to investigate the effects of operating conditions on the optimal refrigerant charge of the gas injection cycle. In the present tests, the heating performance of the gas injection cycle was measured by varying refrigerant charge amount, EEV opening, and compressor frequency at the standard heating condition. The optimal refrigerant charge was very sensitive with openings of the first and second EEVs. On the other hand, the optimal refrigerant charge was not dependent on compressor frequency.